採用恆定電流法進行自動接地電阻測試的適當設計

TOS6200A 專為執行符合 IEC、EN、VDE、BS、UL、JIS 和日本電氣設備安全標準 (EMASL) 等安全標準的 I 類設備接地連接測試而設計。它配備了新型高效電源,體積小巧、重量輕,約為我們傳統產品的一半,同時輸出功率高達 150 VA。採用恆定電流測試方法,即使被測設備的電阻值波動,也無需重置測試電流。測試持續時間可設定為 0.3 秒,使其適用於對測試週期要求較低的生產線測試。
此外,該測試儀設計簡潔易用,配備大尺寸易讀顯示屏,內存可存儲 100 種測試條件,並可將測試條件集成到程序中以實現自動測試。標準配置的 GPIB 和 RS232C 介面允許使用者使用 PC 或其他設備來控制測試條件,例如測試電流、用於判斷的電阻值和測試持續時間,並能夠讀取測量值和測試結果。



  • ● 測試電流值:3 A 至 30 A 交流電/電阻值:0.001 Ω 至 1.200 Ω
    ● 可透過電阻和電壓降來確定。
    ● 偏移量消除功能
    ● 在記憶體中儲存 100 個測試條件
    ● 將測試條件納入程序
    ● 聯繫檢查功能
    ● 配備標準GPIB和RS232C接口
    ● 配備標準測試線(TL11-TOS)

詳細規格

Output

Current setting range *1   3.0 Aac to 31.0 Aac (With respect to resistance resulting in output power of the maximum rated Output or less and an output terminal voltage of 5.4 V or less)
Resolution 0.1A
Accuracy ± (1% of setting + 0.2 A)
Maximum rated output 150 VA (at the output terminals)
Distortion 2% or less (with respect to 0.1 Ω pure resistance load of 10 A or greater)
Frequency   50/60 Hz, sine wave (selectable)
Accuracy ±200 ppm
Open terminal voltage 6 Vrms or less
Output method PWM switching

Output ammeter

Measurement range 0.0 Aac to 33.0 Aac
Resolution 0.1A
Accuracy ± (1% of reading + 0.2 A)
Response Mean value response/rms value display (response time: 200 ms)
Holding function The current measured at the end of test is held during the PASS or FAIL inteval

Output voltmeter

Measurement range 0.00 Vac to 6.00 Vac
Resolution 0.01V
Offset cancel function 0.00 V to 5.40 V (Offset ON/OFF function provided)
Accuracy ± (1% of reading + 0.02 V)
Response Mean value response/rms value display (response time: 200 ms)
Hold feature The voltage measured at the end of test is held during the PASS or FAIL inteval

Ohmmeter *2

Measurement range 0.001 Ω to 1.200 Ω
Resolution 0.001Ω
Offset cancel function 0.000 Ω to 1.200 Ω (Offset ON/OFF function provided)
Accuracy ± (2% of reading + 0.003 Ω)
Holding function The resistance measured at the end of test is held during the PASS interval

Pass/fail judgement function *3

Resistance value-based judgement Window comparator system
· If a resistance value equal to or greater than the upper reference value is detected,a FAILdetermination is returned.
· If a resistance value equal to or less than the lower reference value is detected, a FAIL determination is returned.
· If a resistance value has been judged as FAIL, the tester shuts off the output and generates a FAIL signal.
· If the set time elapses without abnormalities, the tester shuts off the output and generates a PASS signal.
Setting range for the upper reference value (UPPER) 0.001 Ω to 1.200 Ω
Setting range for the lower reference value (LOWER) 0.001 Ω to 1.200 Ω
Resolution 0.001Ω
Judgment accuracy ± (2% of UPPER + 0.003 Ω)
Sampled voltage value-based judgment Window comparator system
· If a voltage value equal to or greater than the upper reference value is detected, a FAIL determination is returned.
· If a voltage value equal to or less than the lower reference value is detected, a FAIL determination is returned.
· If a resistance value has been judged as FAIL, the tester shuts off the output and generates a FAIL signal.
· If the set time elapses without abnormalities, the tester shuts off the output and generates a PASS signal.
Setting range for the upper reference value (UPPER) 0.01 V to 5.40 V
Setting range for the lower reference value (LOWER) 0.01 V to 5.40 V
Resolution 0.01V
Judgment accuracy ± (2% of setting + 0.05 V)
Calibration Calibration is performed with the rms value of the sine wave, using a pure resistance load.
LED PASS Lights for approximately 0.2 sec when the measured value has been judged as PASS. It is lit continuously when the PASS holding time is set to HOLD.
UPPER FAIL Lights if a resistance or voltage value equal to or greater than the upper reference value is detected and judged FAIL.
LOWER FAIL Lights if the resistance or voltage value equal to or less than the lower reference value is detected and judged FAIL.
Buzzer · The buzzer sounds for the pass holding time has been set if the measured value has been judged as PASS.
· The buzzer sounds continuously under the following condition:
The measured value has been judged as PASS when the PASS holding time is set to HOLD.
The measured value has been judged as UPPER FAIL. The measured value has been judged as LOWER FAIL.
· The buzzer volume for FAIL or PASS judgment are adjustable. Note that it cannot be adjusted individually since setting is shared with the setting for PASS.

Power requirement

Input voltage range 85 Vac to 250 Vac
Power consumption No load(READY state) 60 VA or less
Rated load 280 VA max.
Allowable frequency range 47 Hz to 63 Hz
Insulation resistance 30 MΩ min. (500 Vdc), between AC line and chassis
Withstanding voltage 1390 Vac (2 seconds), between AC line and chassis
Earth continuity 25 Aac/ 0.1 Ω max.

*實際規格依型號與選配項目而異,詳情請洽啟宸科技。